Distribution Isolation Transformers (≤1,000 kVA, ≤1.2kV Class)
Autotrnasformers (≤1,000 kVA, ≤1.2kV Class)
General purpose isolation transformers are not optimized for the unique demands of motor drives, such as handling harmonic distortion and voltage spikes. Rex Power Magnetics’ Drive Isolation Transformers are specifically designed to withstand these conditions, making them a safer and more effective choice.
Rex Power Magnetics’ Drive Isolation Transformers are specifically designed to handle the high-frequency harmonic currents associated with variable frequency drives (VFDs) and other motor drive applications. They help reduce line disturbances, protect the drive from voltage spikes, and prevent electrical noise from reaching the power supply
Shielded isolation transformers include a copper electrostatic shield between the primary and secondary windings, which helps reducing capacitive coupling between the windings, attenuating the transfer of high-frequency noise and transients from one system to the next. The primary advantages include superior noise suppression, improved protection against high-voltage spikes, and reduced risk of common-mode interference. The disadvantage is that shielded transformers can be more costly and larger in size compared to their non-shielded counterparts. In applications where high-frequency noise or voltage transients are a concern, the added investment in a shielded transformer is often justified.
When an Isolation Transformer is used in a system with multiple grounding points, it’s essential to review the grounding scheme carefully. Multiple grounding points can create ground loops, leading to unwanted circulating currents and potential equipment damage. It is often recommended to use a single-point grounding strategy for the secondary neutral of the Isolation Transformer and to ensure that the grounding path is low impedance. Any changes to grounding should follow local electrical codes and safety standards.
Voltage regulation refers to the voltage drop on the secondary side of the transformer from no load to full load. The voltage drop is a function of the percentage loading and the power factor of the load. Low voltage distribution isolation transformers generally have a voltage regulation which will range between 1-3% at full load for load with a power factor of 1, and 2-5% at full load for load with a power factor of 0.8.
Isolation Transformers are commonly used to decouple two circuits, providing electrical isolation between the primary and secondary windings. They are typically used to eliminate ground loops, reduce electrical noise, and enhance safety in sensitive equipment such as medical devices, industrial control systems, and power supplies.
Ideally, an RC snubber should be installed as close as possible to the transformer it is designed to protect. For new transformers, if space allows, the snubber can be integrated directly within the transformer enclosure, ensuring a minimal cable length between the snubber and the transformer. In retrofit applications or when a standalone snubber is required, careful attention should be given to minimizing the cable length between the transformer and the snubber to ensure optimal protection.
Since power systems are dynamic and each setup varies, there is no universal recommendation for the maximum acceptable cable length before the snubber’s effectiveness is compromised. A thorough analysis, including Transient Recovery Voltage (TRV) studies, is necessary to assess system-specific parameters and determine how the cable length between the RC snubber and the transformer will affect its performance.
Power systems are inherently dynamic, and each setup differs in terms of load characteristics, equipment ratings, manufacturer specifications, configurations, insulation levels, voltage ranges, and the interconnection of various components.
While standard benchmarks and guidelines exist for designing snubbers, a thorough analysis and Transient Recovery Voltage (TRV) studies are necessary to accurately predict the unique transient voltage levels and frequencies specific to each system. This is due to the fact that no two power systems are exactly alike.
By using the results from TRV studies, the ideal capacitor and resistor values can be sized to enhance the system’s protection.
Dry-type transformers can generally be connected in reverse (back-fed), but there are some precautions to consider:
Always review applicable codes and standards and consult with the local authority having jurisdiction before reverse feeding transformers.
The life expectancy of a dry-type transformer is primarily determined by the insulation system and the operating temperature. According to IEEE Std. C57.96, the deterioration of insulation is directly related to the time and temperature the transformer experiences during operation. Insulation materials degrade faster at higher temperatures, so the transformer’s life expectancy is closely tied to how well it is kept within its design temperature limits.
In most transformers, the highest temperature occurs at a specific point in the windings, known as the hot spot. This area undergoes the most significant wear over time, making it the primary factor in determining the transformer’s ageing process.
All of Rex Power Magnetics’ dry-type transformers are designed using UL-listed insulation systems with a maximum hot spot temperature that ensures a design life of at least 30 years under standard operating conditions (continuous rated load, typical ambient temperatures, and no sustained overloads). Transformers designed with reduced temperature rise can extend this design life expectancy to over 50 years, as operating at lower temperatures slows the insulation’s ageing process.
Factors That Affect Life Expectancy:
By following proper installation and maintenance practices, such as avoiding overloading and ensuring the transformer operates within its designed ambient temperature, you can significantly extend its lifespan. Rex Power Magnetics’ high-quality transformers are built for durability, ensuring reliable performance for decades under standard conditions.
It`s normal for new transformers to release some harmless odors from the varnish impregnation used in the coils for a week or two after energization. Older Transformers can also release some odor if loaded to a higher level than they have experienced previously in their history.
Rex Power Magnetics’ ventilated distribution transformer terminals are rated 90°C. Conductors with at least a 90°C insulation rating at or below their 90°C ampacity rating should be utilized.
In dry-type transformers, the surrounding air plays a critical role in their operation. Generally, low ambient temperatures do not negatively impact an energized transformer, as the no-load losses typically generate enough heat to maintain proper conditions, even in environments as cold as -40°C. However, transformers stored at low temperatures present two primary concerns:
Rex Power Magnetics recommends testing transformers (megger testing), warming them to above 0°C, or following a drying-out procedure if moisture is suspected. Refer to Rex Power Magnetics’ cold start procedures to ensure safe energization in cold conditions. Energizing a transformer with compromised insulation due to moisture can cause damage and potential safety hazards.
The minimum required clearances of a dry type transformer to walls, floors or other equipment must adhere to the local electrical code requirements.
In the absence of such requirements, Rex Power Magnetics recommends that dry type transformers be mounted so that there is an air space of no less than 150mm (6”) between the enclosures, and between the enclosure and any adjacent surface except floors. When the adjacent surface is a combustible material, the minimum permissible separation between the transformer enclosure and the adjacent surface should be 300mm (12”). Where the adjacent surface is the wall on which the transformer is mounted, the minimum permissible separation between the enclosure and the mounting wall should be 6mm (0.25”) so long as the surface is of a non-combustible material.
Any transformer which is not installed and energized immediately should be stored in a dry, clean space having a uniform temperature to prevent condensation on the windings. Dry type transformers with resin dipped or epoxy vacuum impregnated coils can be stored at ambient temperatures as low as -50C. Transformers with encapsulated or epoxy cast coils should not be stored at ambient temperatures below -20C to prevent cracking of the epoxy. Preferably, transformers should be stored in a heated building having adequate air circulation and protected from cement, plaster, paint, dirt, and water or other gases, powders, and dust. The floor on which the transformer is being stored should be resistant to the upward migration of water vapor. Precautions should be taken to prevent storage in an area that water could be present, such as roof leaks, windows, etc. Condensation or absorption of moisture can be greatly reduced by keeping the transformer enclosure 5⁰C-10⁰C above ambient temperature. This can be easily achieved by the installation and energization of space heaters (optional). If the transformer is not furnished with internal space heaters, then external, portable heaters can be used. Note: Lamps or heaters should never come in direct contact with the transformer coil insulation.
It is not advisable to store a dry type transformer outdoors, but in the case that it is unavoidable, protective measures should be taken to prevent moisture and foreign debris from entering the transformer enclosure. The plastic wrapping supplied during shipment should be left in place, and a suitable drying agent such as silica gel packs should be used. The unit should also be checked periodically for indications of condensation on the windings, coil support blocks, core, core clamping system and bus/cables.
Temperature rise refers to average increase of temperature of the transformer windings at full load above the ambient temperature. when operating at full load. In addition to the average temperature rise of the windings, transformers also experience a “hot spot” temperature, which refers to the highest temperature point in the windings.
For example, a transformer with a 220°C insulation system may be designed with a 150°C average temperature rise and a 30°C hot spot allowance. This means that Above a 40C ambient, the total absolute temperature will not exceed 220°C. Transformers with lower temperature insulation systems (180°C or 200°C) will be designed with lower temperature rises (115° or C130°C) and hot spots so they can be installed in the same ambient temperature and still not exceed the temperature rating of the insulation system.
The table below shows the maximum average winding temperature rise, maximum hot spot temperature rise and maximum winding temperature for the most common insulation classes. Note that these are based on a max average ambient of 30°C during any 24-hour period and a maximum ambient of 40°C at any time.
Insulation Class | Insulation Class | Average Winding Temperature Rise |
Hot Spot Temperature Rise |
Maximum Winding Temperature |
Class 180 | F | 115°C | 145°C | 180°C |
Class 200 | N | 130°C | 160°C | 200°C |
Class 220 | H | 150°C | 180°C | 220°C |
Customers occasionally specify a transformer of a particular insulation class to be designed with an average temperature rise below the average temperature rise values shown in the table above. The benefits of doing so include:
Unless designed for special service conditions / environments, below are the standard service conditions for dry type distribution transformers:
To ensure proper operation, avoid installing transformers in environments with excessive moisture, extreme temperatures, or direct sunlight. Maintain recommended clearances and keep all ventilation panels unobstructed.
There are currently no technical whitepapers available for download